http://www.avonelectric.co.nz/images/avon-logo.jpg

LEADING SUPPLIERS AND MANUFACTURERS OF QUALITY
ELECTRIC HEATING, VENTILATION AND ENERGY EFFICIENT SYSTEMS
Ph: 0800 379 247


Swimming Pool Solutions | Heat Recovery Units | Mechanical Dehumidification | Case Studies


SWIMMING POOL CASE STUDIES

PERFORMANCE FIGURES FOR KAWAROA POOL - NEW PLYMOUTH
(Outdoor ambient temperature 5 oC)

CONDITIONS
Outdoor Ambient:
(Air supply to HRV)
Temperature 5 oC corner.gif (59 bytes)
Air Volume 11.4 m3/s
Relative Humidity 80 % tbar.gif (62 bytes)

H R V

 

E f f e c t

Exhaust Air:
(from Pool Hall)
Temperature 28 oC
Air Volume 11.4 m3/s
Relative Humidity 65 %
Heat Exchanger Model Epoxy coated 1000B-2700
Heat Exchanger core width 2700 mm
RESULTS
Pressure drop (supply air) 370 Pa
Pressure drop (exhaust air) 359 Pa
Temperature Efficiency 63 %
Fresh air supply to Pool Hall
(via HRV)
Temperature 19 oC tarrow.gif (65 bytes)
Relative Humidity 32 % carrow.gif (62 bytes)
Recovered Energy
(Kw Effect)
202 kW
Condensation 103.3 litres per hour
These  calculations are based on information provided or reasonably assessed - errors and omissions excepted.

NEXT
NEXT


Kawaroa Pool is a large Community Pool and Leisure Complex built in 1993